Flame retardant test as per IEC 60332-1
| Operating Temp: | -20°C to max.+80°C |
| Nominal voltage: | HO5V-K : 300/500 V HO7V-K : 450/750 V |
| Test voltage: | HO5V-K : 2000 V HO7V-K : 2500 V |
| Insulation resistance: | Min. 10 MΩ x km |
| Min. bending radius: | 4 x cable diameter |
H05V-K, H07V-K
Fixed installation in conduits and under plaster, for appliance wiring and distribution stations
Standard length cable packing:
Coils 100 and 200 m in carton boxes, reels
Technical DataTable | Download Catalog
| HO5V-K (300/500 V) | |||||
| Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | Min insulation resistance at 70°C | |
| Lower limit | Upper limit | ||||
| sqmm | mm | mm | mm | Ω / km | MΩkm |
| 0.50 | 0.60 | 2.10 | 2.50 | 39.00 | 0.013 |
| 0.75 | 0.60 | 2.20 | 2.70 | 26.00 | 0.011 |
| 1.00 | 0.60 | 2.40 | 2.80 | 19.50 | 0.010 |
| HO7V-K (450/750 V) | |||||
| Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | Min insulation resistance at 70°C | |
| Lower limit | Upper limit | ||||
| sqmm | mm | mm | mm | Ω / km | MΩkm |
| 01.50 | 0.70 | 02.80 | 03.40 | 13.300 | 0.0100 |
| 02.50 | 0.80 | 03.40 | 04.10 | 07.980 | 0.0095 |
| 04.00 | 0.80 | 03.90 | 04.80 | 04.950 | 0.0078 |
| 06.00 | 0.80 | 04.40 | 05.30 | 03.300 | 0.0068 |
| 10.00 | 1.00 | 05.70 | 06.80 | 01.910 | 0.0065 |
| 16.00 | 1.00 | 06.70 | 08.10 | 01.210 | 0.0053 |
| 25.00 | 1.20 | 08.40 | 10.20 | 00.780 | 0.0050 |
| 35.00 | 1.20 | 09.70 | 11.70 | 00.554 | 0.0043 |
| 50.00 | 1.40 | 11.00 | 13.90 | 00.386 | 0.0042 |
| 70.00 | 1.40 | 13.20 | 16.00 | 00.272 | 0.0036 |
| 95.00 | 1.60 | 15.10 | 18.20 | 00.206 | 0.0036 |
| 120.00 | 1.60 | 16.70 | 20.20 | 00.161 | 0.0032 |
| 150.00 | 1.80 | 18.60 | 22.50 | 00.129 | 0.0032 |
| 185.00 | 2.00 | 20.60 | 24.90 | 00.106 | 0.0032 |
| 240.00 | 2.20 | 23.50 | 28.40 | 00.081 | 0.0031 |