Flame retardant test as per IEC 60332-1
| Operating Temp: | -30°C to +90°C |
| Nominal voltage: | HO5V2-U : 300/500 V HO7V2-U : 450/750 V |
| Test voltage: | HO5V2-U : 2000 V HO7V2-U : 2500 V |
| Insulation resistance: | 20 MΩ x km |
| Min. bending radius: | 4 x cable diameter |
HO5V2-U, HO7V2-U
For internal wiring of appliances as well as installation in an electrical conduit pipe either on or underneath plaster
Standard length cable packing:
Coils 100 and 200 m in carton boxes, reels
Technical DataTable | Download Catalog
| HO5V2-U (300/500 V) | |||||
| Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | Min insulation resistance at 90°C | |
| Lower limit | Upper limit | ||||
| sqmm | mm | mm | mm | Ω / km | MΩkm |
| 0.50 | 0.60 | 1.90 | 2.30 | 36.00 | 0.014 |
| 0.75 | 0.60 | 2.10 | 2.50 | 24.50 | 0.013 |
| 1.00 | 0.60 | 2.20 | 2.70 | 18.10 | 0.011 |
| HO7V2-U (450/750 V) | |||||
| Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | Min insulation resistance at 90°C | |
| Lower limit | Upper limit | ||||
| sqmm | mm | mm | mm | Ω / km | MΩkm |
| 1.50 | 0.70 | 2.60 | 3.20 | 12.10 | 0.011 |
| 2.50 | 0.80 | 3.20 | 3.90 | 07.41 | 0.010 |