generally conforms to, CENELEC HD 22.1.S2, DIN VDE 0282 part 810, IEC 245, CEI 20-19 & BS 6007, BS 6899
Operating Temp: | -40°c to max.+90°C |
Nominal voltage: | 1100 V |
Test voltage: | 3000 V |
Min. bending radius: | 6 x cable diameter |
Flame propagation: | Flame retardant test as per IEC 60332-1 |
The PVC insulated and sheathed 3 core flat cables are used for giving electricals connection to the submersible pump motors. These are manufactured keeping in mind the severe, tough and difficult conditions in which they have to operate. The slot available in the tube well being narrow the shape of the cables has to be suited for such an application. These cables conform to and are marked IS 694:1990 upto 4.00 sq. mm. The sizes above 4.00 sq. mm. cables generally conform to IS 694:1990.
Technical DataTable | Download Catalog
Conductor | Rubber Insulation | Rubber Sheath | Conductor Resistance at 20°C (max) | Current Rating at 40°C | ||||
Nominal Area in | Nos. & Dia. of wire | Nominal Thickness | Nominal Core Dia. | Nominal Thickness | Approx. Overall Dimensions | |||
Thickness | Width | |||||||
Sq. mm. | Nos./mm | mm | mm | mm | mm | mm | O/km | Amps. |
01.50 | 22/0.30 | 0.80 | 03.25 | 1.15 | 06.00 | 12.80 | 12.10 | 014 |
02.50 | 36/0.30 | 0.90 | 03.84 | 1.15 | 06.40 | 14.60 | 07.41 | 018 |
04.00 | 56/0.30 | 1.00 | 04.50 | 1.15 | 07.40 | 16.80 | 04.95 | 026 |
06.00 | 84/0.30 | 1.00 | 05.30 | 1.15 | 07.90 | 18.70 | 03.30 | 031 |
10.00 | 140/0.30 | 1.00 | 06.50 | 1.40 | 09.90 | 23.70 | 01.91 | 042 |
16.00 | 224/0.30 | 1.00 | 08.00 | 1.40 | 11.40 | 28.00 | 01.21 | 057 |
25.00 | 350/0.30 | 1.20 | 10.10 | 2.00 | 14.70 | 35.50 | 00.78 | 072 |
35.00 | 490/0.30 | 1.20 | 11.30 | 2.00 | 16.20 | 39.50 | 00.55 | 090 |
50.00 | 703/0.30 | 1.40 | 13.60 | 2.20 | 18.30 | 45.50 | 00.39 | 115 |
70.00 | 988/0.30 | 1.40 | 15.30 | 2.20 | 20.00 | 51.00 | 00.27 | 143 |
95.00 | 1349/0.30 | 1.60 | 18.00 | 2.40 | 23.50 | 60.00 | 00.21 | 165 |
Rubber Flat - 4 core | ||||||||
Conductor | Rubber Insulation | Rubber Sheath | Conductor Resistance at 20°C (max) | Current Rating at 40°C | ||||
Nominal Area in | Nos. & Dia. of wire | Nominal Thickness | Nominal Core Dia. | Nominal Thickness | Approx. Overall Dimensions | |||
Thickness | Width | |||||||
Sq. mm. | Nos./mm | mm | mm | mm | mm | mm | O/km | Amps. |
01.50 | 22/0.30 | 0.80 | 03.25 | 1.30 | 06.00 | 15.80 | 12.10 | 014 |
02.50 | 36/0.30 | 0.90 | 03.84 | 1.30 | 06.50 | 18.00 | 07.41 | 018 |
04.00 | 56/0.30 | 1.00 | 04.50 | 1.45 | 07.60 | 21.00 | 04.95 | 026 |
06.00 | 84/0.30 | 1.00 | 05.30 | 1.50 | 07.90 | 24.30 | 03.30 | 031 |
10.00 | 140/0.30 | 1.00 | 06.50 | 1.80 | 09.90 | 29.70 | 01.91 | 042 |
16.00 | 224/0.30 | 1.00 | 08.00 | 1.95 | 11.80 | 36.00 | 01.21 | 057 |
25.00 | 350/0.30 | 1.20 | 10.10 | 2.00 | 14.70 | 45.10 | 00.78 | 072 |
35.00 | 490/0.30 | 1.20 | 11.50 | 2.00 | 16.20 | 50.10 | 00.55 | 090 |
50.00 | 703/0.30 | 1.40 | 13.60 | 2.20 | 18.30 | 58.10 | 00.39 | 115 |
70.00 | 988/0.30 | 1.40 | 15.30 | 2.20 | 20.00 | 66.50 | 00.27 | 143 |
95.00 | 1349/0.30 | 1.60 | 18.00 | 2.40 | 23.50 | 77.30 | 00.21 | 165 |