Manufactured from bright annealed 99.97% pure bare copper conductors these cables offer low conductor resistance. These wires are insulated with a special grade PVC compound formulated and manufactured in-house. The tough robust outer PVC jacket protects it from the oils, greases, various chemicals and abrasions giving long life and electrical safety.
Working Voltage : | Up to 1100 V. | ||||||
Temperature range : | -15° C to + 70° C | ||||||
Sizes : | 0.50 to 4.00 Sq. mm in 2 core to 19 cores & 6.00 to 120.00 Sq. mm in 3 core and 4 core. | ||||||
Color codes : | Black and Grey outer sheath | ||||||
|
|||||||
Specification : | IS : 694 | ||||||
Packing : | In 90-meters coils, Higher sizes on drums | ||||||
These multi core flexible cables are used for wiring in control panels, machines and various electrical installations in dry and damp interiors especially under typical industrial environmental conditions.
Technical DataTable | Download Catalog
POWER CAB plain copper conductor PVC insulated & sheathed 650/1100 V., Multi Core Flexible Cables as per IS-694/2010 with ISI mark
Cond AreaSq.mm | Constru.No./Dia. | Cond.Dia mm. | Max.Dc resistance Ohm/Km at 20 °C | Insulation Thickness Nominal in mm. | Core Diameter in mm. | Nominal Thickness of Insulation in mm | Over All Diameter Thickness in mm. | Current Rating Amp. | ||||
--- | --- | --- | --- | --- | --- | 2 core | 3 Core | 4 Core | 2 Core | 3 Core | 4 Core | --- |
00.50 | 016/0.20 | 00.94 | 39.00 | 0.60 | 02.35 | 0.90 | 0.90 | 0.90 | 06.70 | 07.05 | 07.70 | 004.00 |
00.75 | 024/0.20 | 01.20 | 26.00 | 0.60 | 02.60 | 0.90 | 0.90 | 0.90 | 09.35 | 07.60 | 08.30 | 007.00 |
01.00 | 032/0.20 | 01.34 | 19.50 | 0.60 | 02.80 | 0.90 | 0.90 | 0.90 | 08.05 | 07.90 | 08.65 | 011.00 |
01.50 | 048/0.20 | 01.64 | 13.30 | 0.60 | 03.00 | 0.90 | 0.90 | 0.90 | 07.50 | 08.50 | 09.30 | 014.00 |
02.50 | 080/0.20 | 02.08 | 07.95 | 0.70 | 03.65 | 1.00 | 1.00 | 1.00 | 07.20 | 09.90 | 10.90 | 019.00 |
04.00 | 056/0.30 | 02.61 | 04.95 | 0.80 | 04.40 | 1.00 | 1.00 | 1.00 | 06.70 | 11.85 | 13.05 | 026.00 |
06.00 | 085/0.30 | 03.50 | 03.30 | 0.80 | 05.10 | 1.15 | 1.15 | 1.40 | 12.60 | 13.40 | 15.20 | 031.00 |
10.00 | 140/0.30 | 04.60 | 01.91 | 1.00 | 06.60 | 1.40 | 1.40 | 1.40 | 16.00 | 17.00 | 18.80 | 042.00 |
16.00 | 226/0.30 | 06.00 | 01.21 | 1.00 | 08.00 | 1.40 | 1.40 | 1.40 | 18.80 | 21.10 | 22.20 | 057.00 |
25.00 | 255/0.30 | 07.60 | 00.78 | 1.20 | 10.00 | 2.00 | 2.00 | 2.00 | 24.00 | 25.60 | 28.20 | 071.00 |
35.00 | 220/0.45 | 08.70 | 01.55 | 1.20 | 11.10 | 2.00 | 2.00 | 2.00 | 26.30 | 28.00 | 31.00 | 091.00 |
50.00 | 325/0.45 | 10.60 | 01.39 | 1.40 | 13.40 | 2.00 | 2.00 | 2.00 | 30.90 | 33.00 | 36.50 | 120.00 |
POWER CAB Multi Core Flexible Cables(6 cores to 19 cores) as per IS-694/2010
Area Sq.mm. |
00.50 |
00.75 |
01.00 |
01.50 |
02.50 |
04.00 |
|
General Construction No/Dia. |
16/0.2 |
24/0.2 |
32/0.2 |
48/0.2 |
80/0.2 |
56/0.3 |
|
Conductor Dia in mm. |
00.94 |
01.20 |
01.34 |
01.64 |
02.08 |
02.61 |
|
Avg. Insu. Thickness in mm. |
00.60 |
00.60 |
00.60 |
00.60 |
00.70 |
00.80 |
|
Core Dia in mm. |
20.20 |
20.60 |
20.60 |
20.60 |
30.50 |
40.30 |
|
No of cores |
|
|
|
|
|
|
|
6 |
Avg Sheath thickness mm.App. overall Dia mm. |
00.90 08.50 |
01.00 09.50 |
01.00 09.80 |
01.00 10.70 |
01.10 12.70 |
01.20 15.30 |
7 |
Avg Sheath thickness mm.App. overall Dia mm. |
00.90 08.50 |
01.00 09.50 |
01.00 09.80 |
01.00 10.70 |
01.10 12.70 |
01.20 15.30 |
8 |
Avg Sheath thickness mm.App. overall Dia mm. |
01.00 09.30 |
01.00 10.40 |
01.00 10.70 |
01.10 11.90 |
01.20 14.10 |
01.30 16.90 |
10 |
Avg Sheath thickness mm.App. overall Dia mm. |
01.00 10.80 |
01.10 12.20 |
01.10 12.60 |
01.10 13.80 |
01.30 17.20 |
01.40 20.70 |
12 |
Avg Sheath thickness mm.App. overall Dia mm. |
01.00 11.20 |
01.10 12.60 |
01.10 13.00 |
01.10 14.30 |
01.30 17.20 |
01.40 20.70 |
14 |
Avg Sheath thickness mm.App. overall Dia mm. |
01.10 12.00 |
01.10 13.30 |
01.10 13.70 |
01.20 15.20 |
01.30 18.10 |
01.40 21.80 |
16 |
Avg Sheath thickness mm.App. overall Dia mm. |
01.10 12.60 |
01.20 14.20 |
01.20 14.60 |
01.20 16.00 |
01.40 19.30 |
01.50 23.20 |
19 |
Avg Sheath thickness mm.App. overall Dia mm. |
01.10 13.20 |
01.20 14.90 |
01.30 18.20 |
01.40 20.20 |
01.40 23.80 |
01.50 28.80 |
24 |
Avg Sheath thickness mm.App. overall Dia mm. |
01.20 15.60 |
01.30 17.60 |
01.30 17.60 |
01.40 20.20 |
01.40 25.70 |
01.50 30.60 |
30 |
Avg Sheath thickness mm.App. overall Dia mm. |
01.30 16.80 |
01.30 18.70 |
01.30 19.30 |
01.40 21.50 |
01.40 27.00 |
01.50 32.00 |
-- |
Max.Conductor Resistance In Ohm/Km.at20°C |
39.00 |
26.00 |
19.50 |
13.30 |
07.98 |
04.95 |
-- |
Recommended Current Rating in amp. |
4 |
7 |
11 |
14 |
19 |
26 |