generally conforms to IS 694, BS 6004, IEC 60227, DIN VDE 0281-3, IS 8130 & IS 5831
Manufactured from bright annealed 99.97% pure bare copper conductors these cables have low conductor resistance resulting in power saving. These wires are insulated with a special grade PVC compound formulated and manufactured in-house. The insulation is far superior in terms of critical oxygen and temperature index as also in light transmission and acid gas generation. The skin coloration offers high insulation resistance and long life.
Operating Temp: | -15°c to max.+70°C |
Nominal voltage: | 1100 V |
Test voltage: | 3000 V |
Range of product: | 1 sq. mm to 6 sq. mm |
Min. bending radius: | 8 x cable diameter |
FRLS-H properties: | Flame retardant test as per IS 10810-58, 59,64, IEC 60332-1, ASTM-D 2843 |
This is a premium product of electrical wires from 'POWER CAB'. These cables are ideals for wiring in residential and commercial complexes, high-rise buildings, hotels, hospitals, schools, colleges etc. Where density of people is high. During a fire these cables not only emit less smoke and toxic hydrochloric acid gas but also retard the spread of fire enabling those trapped inside to escape safely.
Technical DataTable | Download Catalog
FRLS House Wires | ||||||
Nominal cross sectional area of conductor | Number/Nominal dia of strands | Nominal insulation thickness | Max.Overall diameter | Max conductor resistance at 20°C | ||
Nominal cur Rat 3 phase | Nearesr Equiv Size | |||||
sqmm | mm | mm | mm | O/km | mm | |
1.00 | 14/0.30* | 0.70 | 2.80 | 18.10 | 12.00 | 1/1.13 |
1.50 | 22/0.30* | 0.70 | 3.00 | 12.10 | 16.00 | 3/0.80 |
2.50 | 36/0.30* | 0.80 | 3.70 | 07.41 | 22.00 | 3/1.04 |
4.00 | 56/0.30** | 0.80 | 4.30 | 04.95 | 29.00 | 7/0.85 |
6.00 | 85/0.30** | 0.80 | 5.30 | 03.30 | 37.00 | 7/1.04 |