Zero halogen IEC 60754-2, Flame retardant test as per IEC 60332-1
Operating Temp: | -30°C to +90°C |
Nominal voltage: | HO5Z-K : 300/500 V HO7Z-K : 450/750 V |
Test voltage: | HO5Z-K : 2500 V HO7Z-K : 2500 V |
Insulation resistance: | Min. 10 MΩ x km |
Min. bending radius: | 4 x cable diameter |
HO5Z-K, H07Z-K
Fixed installation in conduits and under plaster, for appliance wiring and distribution stations For wiring of lamps, devices, switchgear cabinets and distribution boxes
Standard length cable packing:
Coils 100 and 200 m in carton boxes, reels
Technical DataTable | Download Catalog
HO5Z-K (300/500 V) | |||
Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C |
sqmm | mm | mm | Ω / km |
0.50 | 0.50 | 2.30 | 39.00 |
0.75 | 0.60 | 2.50 | 26.00 |
1.00 | 0.60 | 2.60 | 19.50 |
HO7Z-K (450/750 V) | |||||||
Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | ||||
sqmm | mm | mm | Ω / km | ||||
01.50 | 0.70 | 03.50 | 13.300 | ||||
02.50 | 0.80 | 04.00 | 07.980 | ||||
04.00 | 0.80 | 04.80 | 04.950 | ||||
06.00 | 0.80 | 06.00 | 03.300 | ||||
10.00 | 1.00 | 06.70 | 01.910 | ||||
16.00 | 1.00 | 08.20 | 01.210 | ||||
25.00 | 1.20 | 10.20 | 00.780 | ||||
35.00 | 1.20 | 11.50 | 00.554 | ||||
50.00 | 1.40 | 13.60 | 00.386 | ||||
70.00 | 1.40 | 16.00 | 00.272 | ||||
95.00 | 1.60 | 18.40 | 00.206 | ||||
120.0 | 1.60 | 20.30 | 00.161 | ||||
150.0 | 1.80 | 22.70 | 00.129 | ||||
185.0 | 2.00 | 25.30 | 00.106 | ||||
240.0 | 2.20 | 28.30 | 00.081 |