Flame retardant test as per IEC 60332-1
Operating Temp: | -20°c to max.+80°C |
Nominal voltage: | HO5V-U : 300/500 V HO7V-U : 450/750 V |
Test voltage: | HO5V-U : 2000 V HO7V-U : 2500 V |
Insulation resistance: | Min. 10 MO x km |
Min. bending radius: | 4 x cable diameter |
H05V-U, H07V-U
Fixed installation in conduits and under plaster, for appliance wiring and distribution stations
Standard length cable packing:
Coils 100 and 200 m in carton boxes, reels
Technical DataTable | Download Catalog
HO5V-U (300/500 V) | |||||
Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | Min insulation resistance at 70°C | |
Lower limit | Upper limit | ||||
sqmm | mm | mm | mm | Ω / km | MΩkm |
0.50 | 0.60 | 1.90 | 2.30 | 36.00 | 0.014 |
0.75 | 0.60 | 2.10 | 2.50 | 24.50 | 0.013 |
1.00 | 0.60 | 2.20 | 2.70 | 18.10 | 0.011 |
HO7V-U (450/750 V) | |||||
Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | Min insulation resistance at 70°C | |
Lower limit | Upper limit | ||||
sqmm | mm | mm | mm | Ω / km | MΩkm |
01.50 | 0.70 | 2.60 | 3.20 | 12.10 | 0.0110 |
02.50 | 0.80 | 3.20 | 3.90 | 07.41 | 0.0100 |
04.00 | 0.80 | 3.60 | 4.40 | 04.61 | 0.0087 |
06.00 | 0.80 | 4.10 | 5.00 | 03.08 | 0.0074 |
10.00 | 1.00 | 5.30 | 6.40 | 01.83 | 0.0072 |