Fine Stranded Copper (Class 5 - Flexible Plain Copper) to VDE 0295 IEC 60228
HO5VVF : PVC
HO5V2V2F : Heat Resistant PVC
White, Black, Blue or as per party order
Operating Temp: | H05VV-F -20°c to +80°C H05V2V2-F -20°c to +90°C |
Nominal voltage : | H05VV-F : 300/500 V H05V2V2-F : 300/500 V |
Test voltage : | H05VV-F : 2.5KV H05V2V2-F : 2.5KV |
Insulation resistance : | Min. 20 MΩ x km |
Min. bending radius : | 7 x cable diameter |
H05VV-F, H05V2V2-F
H05VV-F AND H05V2V2-F cordage is a flexible PVC insulated, PVC jacketed harmonized cord recommended for use in electronic and electrical equipment such as office.
Standard length cable packing:
100, 200, 500, 1000 m. in reels
Technical DataTable | Download Catalog
H05VV-F (300/500 V) | |||||||||||||||
Nominal cross sectional area of conductor | Nominal insulation thickness | Nominal sheath thickness in mm | Max overall diameter in mm | Max conductor resistance at 20°C | Min insulation resistance at 70°C | ||||||||||
2 core | 3 core | 4 core | 5 core | 2 core | 3 core | 4 core | 5 core | ||||||||
Lower limit | Upper limit | Lower limit | Upper limit | Lower limit | Upper limit | Lower limit | Upper limit | ||||||||
sqmm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | Ω/km | MΩkm |
0.75 | 0.60 | 0.80 | 0.80 | 0.80 | 0.90 | 5.70 | 07.20 | 06.00 | 07.60 | 06.60 | 08.30 | 07.40 | 09.30 | 26.00 | 0.011 |
1.00 | 0.60 | 0.80 | 0.80 | 0.90 | 0.90 | 5.90 | 07.50 | 06.30 | 08.00 | 07.10 | 09.00 | 07.80 | 09.80 | 19.50 | 0.010 |
1.50 | 0.70 | 0.80 | 0.90 | 1.00 | 1.10 | 6.80 | 08.60 | 07.40 | 09.40 | 08.40 | 10.50 | 09.30 | 11.60 | 13.30 | 0.010 |
2.50 | 0.80 | 1.00 | 1.00 | 1.10 | 1.20 | 8.40 | 10.60 | 09.20 | 11.40 | 10.10 | 12.50 | 11.20 | 13.90 | 07.98 | 0.010 |
4.00 | 0.80 | 1.10 | 1.20 | 1.20 | 1.40 | 9.70 | 12.10 | 10.50 | 13.10 | 11.50 | 14.30 | 13.00 | 16.10 | 04.95 | 0.008 |
H05V2V2-F (300/500 V) | |||||||||||||||
Nominal cross sectional area of conductor | Nominal insulation thickness | Nominal sheath thickness in mm | Max overall diameter in mm | Max conductor resistance at 20°C | Min insulation resistance at 90°C | ||||||||||
2 core | 3 core | 4 core | 5 core | 2 core | 3 core | 4 core | 5 core | ||||||||
Lower limit | Upper limit | Lower limit | Upper limit | Lower limit | Upper limit | Lower limit | Upper limit | ||||||||
sqmm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | Ω/km | MΩkm |
0.75 | 0.60 | 0.80 | 0.80 | 0.80 | 0.90 | 5.70 | 07.20 | 06.00 | 07.60 | 06.60 | 08.30 | 07.40 | 09.30 | 26.00 | 0.011 |
1.00 | 0.60 | 0.80 | 0.80 | 0.90 | 0.90 | 5.90 | 07.50 | 06.30 | 08.00 | 07.10 | 09.00 | 07.80 | 09.80 | 19.50 | 0.010 |
1.50 | 0.70 | 0.80 | 0.90 | 1.00 | 1.10 | 6.80 | 08.60 | 07.40 | 09.40 | 08.40 | 10.50 | 09.30 | 11.60 | 13.30 | 0.010 |
2.50 | 0.80 | 1.00 | 1.00 | 1.10 | 1.20 | 8.40 | 10.60 | 09.20 | 11.40 | 10.10 | 12.50 | 11.20 | 13.90 | 07.98 | 0.010 |
4.00 | 0.80 | 1.10 | 1.20 | 1.20 | 1.40 | 9.70 | 12.10 | 10.50 | 13.10 | 11.50 | 14.30 | 13.00 | 16.10 | 04.95 | 0.008 |