Flame retardant test as per IEC 60332-1
Operating Temp: | -30°C to +90°C |
Nominal voltage: | HO5V2-R : 300/500 V HO7V2-R : 450/750 V |
Test voltage: | HO5V2-R : 2000 V HO7V2-R : 2500 V |
Insulation resistance: | 20 MΩ x km |
Min. bending radius: | 4 x cable diameter |
HO5V2-R, HO7V2-R
For internal wiring of appliances as well as installation in an electrical conduit pipe either on or underneath plaster
Standard length cable packing:
Coils 100 and 200 m in carton boxes, reels
Technical DataTable | Download Catalog
HO5V2-R (300/500 V) | |||||
Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | Min insulation resistance at 90°C | |
Lower limit | Upper limit | ||||
sqmm | mm | mm | mm | Ω / km | MΩkm |
0.50 | 0.60 | 2.00 | 2.40 | 36.00 | 0.014 |
0.75 | 0.60 | 2.20 | 2.60 | 24.50 | 0.012 |
1.00 | 0.60 | 2.30 | 2.80 | 18.10 | 0.011 |
HO7V2-R (450/750 V) | |||||
Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | Min insulation resistance at 90°C | |
Lower limit | Upper limit | ||||
sqmm | mm | mm | mm | Ω / km | MΩkm |
01.50 | 0.70 | 2.70 | 03.30 | 12.100 | 0.0100 |
02.50 | 0.80 | 3.30 | 04.00 | 07.410 | 0.0099 |
04.00 | 0.80 | 3.80 | 04.60 | 04.610 | 0.0082 |
06.00 | 0.80 | 4.30 | 05.20 | 03.080 | 0.0070 |
10.00 | 1.00 | 5.60 | 06.70 | 01.830 | 0.0067 |
16.00 | 1.00 | 6.40 | 07.80 | 01.150 | 0.0056 |
25.00 | 1.20 | 8.10 | 09.70 | 00.727 | 0.0053 |
35.00 | 1.20 | 9.00 | 10.90 | 00.524 | 0.0046 |