Flame retardant test as per IEC 60332-1
Operating Temp: | -30°C max. +90°C |
Nominal voltage: | HO5V2-K : 300/500 V HO7V2-K : 450/750 V |
Test voltage: | HO5V2-K : 2000 V HO7V2-K : 2500 V |
Insulation resistance: | 20 MΩ x km |
Min. bending radius: | 4 x cable diameter |
HO5V2-K, HO7V2-K
For internal wiring of appliances as well as installation in an electrical conduit pipe either on or underneath plaster
Standard length cable packing:
Coils 100 and 200 m in carton boxes, reels
Technical DataTable | Download Catalog
HO5V2-K (300/500 V) | |||||
Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | Min insulation resistance at 90°C | |
Lower limit | Upper limit | ||||
sqmm | mm | mm | mm | Ω / km | MΩkm |
0.50 | 0.60 | 2.10 | 2.50 | 39.00 | 0.013 |
0.75 | 0.60 | 2.20 | 2.70 | 26.00 | 0.011 |
1.00 | 0.60 | 2.40 | 2.80 | 19.50 | 0.010 |
HO7V2-K (450/750 V) | |||||
Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | Min insulation resistance at 90°C | |
Lower limit | Upper limit | ||||
sqmm | mm | mm | mm | Ω / km | MΩkm |
01.50 | 0.70 | 2.80 | 03.40 | 13.300 | 0.0100 |
02.50 | 0.80 | 3.40 | 04.10 | 07.980 | 0.0095 |
04.00 | 0.80 | 3.90 | 04.80 | 04.950 | 0.0078 |
06.00 | 0.80 | 4.40 | 05.30 | 03.300 | 0.0068 |
10.00 | 1.00 | 5.70 | 06.80 | 01.910 | 0.0065 |
16.00 | 1.00 | 6.70 | 08.10 | 01.210 | 0.0053 |
25.00 | 1.20 | 8.40 | 10.20 | 00.780 | 0.0050 |
35.00 | 1.20 | 9.70 | 11.70 | 00.554 | 0.0043 |