Flame retardant test as per IEC 60332-1
Operating Temp: | -40°c to +110°C |
Nominal voltage: | HO5G-K : 300/500 V HO7G-K : 450/750 V |
Test voltage: | HO5G-K : 2000 V HO7G-K : 2500 V |
Insulation resistance: | Min. 10 MΩ x km |
Min. bending radius: | 5 x cable diameter |
HO5G-K, HO7G-K
For inside wiring of witch board and distributors as well as of operating parts such as in or on lights with normal voltage up to 1100 V
Standard length cable packing:
Coils 100 and 200 m in carton boxes, reels
Technical DataTable | Download Catalog
HO5G-K (300/500 V) | |||||
Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | ||
Lower limit | Upper limit | ||||
sqmm | mm | mm | mm | Ω / km | |
0.50 | 0.60 | 2.00 | 2.40 | 39.00 | |
0.75 | 0.60 | 2.10 | 2.60 | 26.00 | |
1.00 | 0.60 | 2.30 | 2.70 | 19.50 |
HO7G-K (450/750 V) | |||||
Nominal cross sectional area of conductor | Nominal insulation thickness | Mean overall diameter | Max conductor resistance at 20°C | ||
Lower limit | Upper limit | ||||
sqmm | mm | mm | mm | Ω/ km | |
01.50 | 0.70 | 03.00 | 03.70 | 13.300 | |
02.50 | 0.80 | 03.60 | 04.50 | 07.980 | |
04.00 | 0.80 | 04.30 | 05.40 | 04.950 | |
06.00 | 0.80 | 04.80 | 06.00 | 03.300 | |
10.00 | 1.00 | 06.00 | 07.60 | 01.910 | |
16.00 | 1.00 | 07.10 | 08.90 | 01.210 | |
25.00 | 1.20 | 08.80 | 11.00 | 00.780 | |
35.00 | 1.20 | 10.10 | 12.60 | 00.554 | |
50.00 | 1.40 | 11.90 | 14.90 | 00.386 | |
70.00 | 1.40 | 13.60 | 17.00 | 00.272 | |
95.00 | 1.60 | 15.20 | 19.30 | 00.206 | |
120.0 | 1.60 | 17.10 | 21.40 | 00.161 | |
150.0 | 1.80 | 19.00 | 23.80 | 00.129 | |
185.0 | 2.00 | 21.00 | 26.30 | 00.106 | |
240.0 | 2.20 | 23.90 | 29.40 | 00.081 |